Software Change For VFD Drives FOR ACS800 1.

Restore the original factory settings: Set the parameter 99.03 APPLIC RESTORE to YES 2. Make inverter data group (group 112) accessible Enter the code 564 at 16.03 PASS CODE) 3. Choose kVA value and voltage class of the inverter For Standard Application software versions up to ASXR7260: - Set the correct value at 112.6 INVERTER RECONFIG (for Standard Application software versions up to ASXR7260) For Standard Application software versions from ASXR7270 onwards: - Set parameter 112.19 to "srdemo" for ACS800 Demo unit - Set the correct value at 112.20 for 220V units - Set the correct value at 112.21 for 400V units - Set the correct value at 112.22 for 500V units - Set the correct value at 112.23 for 690V units 4. Switch power off and then on

ACS550 1.Put in Local Mode 2.Select10.1 and press lower,upper & exit 3.Par 105.09 change rating 4.par 105.02 make it 1 5.105.11 make it 4012 6.Check the rating in 33.04

START INHIBIT TO PREVENT THE DRIVE ACS 550 FROM RE-STARTING WHEN EM STOP PUSH BUTTON IS RELESAED OR A FAULT IS

ware versions up to ASXR7260)

TTON IS RELESAED OR A FAULT IS RESET GO TO GROUP 21 AND ENABLE THE PARAMETER 2108 START INHIBIT

108 START INHIBIT