Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 1 / 25 : 27-Jun-1995

MCS - LCB_II
List of Installation Parameters

Authorization Date D1: 27-Jun-1995 Running on PCB: GCA 21240 D1 - D3 GDA 21240 D1 - D3 GAA 30082 BAC

Software Version: Document Revision:


24 - May - 93 03 - Dec - 93 29 - Apr - 94 02 - Jun - 94 16 - Jun - 94 17 - Jan - 95

- Original Document - OTIS 2000 features add. - Triplex parameter added - Secure Access revised - BSM mode added - MCS220M, LSVF-W, ELD, REM III added 06 - Jun - 95 GAA 30082 BAB A. Gerwing - not distributed 27 - Jun - 95 GAA 30082 BAC A.Gerwing - CPC-TYP, N+2, ELD-MSG, ELD-DOOR GAA 30082 AAA GAA 30082 AAB GAA 30082 AAC GAA 30082 AAD GAA 30082 AAE GAA 30082 BAA

J. Schulte A.Gerwing M. Hnida M. Hnida J. Schulte J. Schulte

Copyright 1995, OTIS GmbH Berlin No part of this document may be copied or reproduced in any form or by any means without the prior written consent of OTIS GmbH.

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 2 / 25 : 27-Jun-1995

System:
No.
0

Version: GAA 30082 BAC Default


2 Top position: 1 (1) 31 Lobby position: 0 (1) 31 Bottom position: 0 (1) 30 Cafeteria Position: 0 (1) 31 > 31 Disabled Operation FCL/DCL/SAPB: 0 FCL 1 DCL 2 SAPB Enable BSM mode (for DCL: both Up- and Down Hall Calls at lobby): 0 Disabled 1 Enabled General configuration: 0 ETO 1 NAO Type of serial Position Indicator: 0 7/16 Segment 1 Multil. 2 Australian Dot Matrix 3 Australian Dot Matrix with CUDL/CDDL 4 OTIS 2000: LCD and ELD front door movement time: opening 0 (0.1) 10.0 s 0 = automatic (not yet implem.) front door movement time: closing 0 (0.1) 10.0 s 0 = automatic (not yet implem.) rear door movement time: opening 0 (0.1) 10.0 s 0 = automatic (not yet implem.)

Symbol
TOP

Purpose and Range

LOBBY

BOTTOM

CFT-P

255

OPERAT

EN-BSM

CONFIG

PI

ELD-fOPG

20

ELD-fCLG

20

10

ELD-rOPG

20

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 3 / 25 : 27-Jun-1995

System (continued):
No.
11

Version: GAA 30082 BAC Purpose and Range


rear door movement time: closing 0 (0.1) 10.0 s 0 = automatic (not yet implem.) set Language for ELD: 0 (1) 19 0 SwiGer, 1 SwiFRA, 5 UK, 6 Spain, 10 Sweden, 11 Luxem, 15 Denmar, 16 SthAfr,

Symbol
ELD-rCLG

Default
20

12

ELD-LNG

2 7 12 17

SwiIta, Nether, Belg, Finlnd,

3 8 13 18

Fra, Ger, Por, Ara,

4 9 14 19

Italy, Aus, Egy, Kuw

13

ELD-Sym1

Enable Non-Smoking symbol: 0 Disabled 1 symbol is displayed select type of door display: 0: 1 COP for 1 door or 2 COPs for 2 doors 1: only 1 COP for 2 doors enables customer messages: 0: no customer messages are displayed by ELD 1: customer messages are enabled (use SETUP-ELD to define the texts) Enable SFR (signal flicker): 0 Disabled 1 Enabled FAN (LR) time: 0 (1) 255 s Enable Hall Lanterns on car calls: 0 Disabled 1 HLC 2 HL also during closing 3 HLC and during door closing Hall Direction Lantern Type of OTIS 2000 Hall Button Box: 0 Direction Indicator 1 Hall Lantern Hall Lantern/Gong Setup: 0 HL/G at same pins 1 HL/G at 1 2/3 4 2 HL/G at 3 4/1 2

R) R) R) R) R) R) R) R)

14

ELD-DOOR

15

ELD-MSG

16

EN-SFR

17

LR-T

20

18

EN-HLC

19

HDL-TY

20

HL-SET

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 4 / 25 : 27-Jun-1995

Version: GAA 30082 BAC

System (continued):
No.
21

Symbol
CR-DIR

Default
0

Purpose and Range


Correction Fast Run Preferred Direction: 0 Down 1 Up Enable Reduced Run (RR): 0 Disabled 1 Enabled (short or medium run) Use DZ for SL counting (for Short Run): 0 Disabled 1 Enabled Enable DZI (Door Zone Indicator): 0 Disabled 1 Enabled (only if no Door ByPass) Define ERO type 0 without limit 1 with limit at terminal landings (same as TCI-limit) 2 ERO-input disabled (for LCB_II version D2) Enable C-Circuit Check: 0 Disabled 1 Enabled select use of MD input (P7:9, only MCS220M): 0 not connected 1 MD: DCS-input for Multi Door (manual plus autom. landing doors) 2 AES: ES-input if RSS or ESB is used select use of CPC outputs: 0 car position contact 1 car here light 2 french SSM enable 3 wire buttons: 0 normal car and hall buttons 1 3 wire car buttons 1 3 wire hall buttons 1 3 wire car and hall buttons

22

EN-RR

23

DZCNT

24

EN-DZI

25

ERO-TYP

R) R)
26 C-CHK 0

27

MD/AES

R) R) R) R) R) R) R) R) R) R) R)
28 CPC-TYP 0

29

N+2 WIRE

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 5 / 25 : 27-Jun-1995

OCSS:
No.
0

Version: GAA 30082 BAC Default


20 Car Call Preference: 0 (0.1) 25.5 s Automatic Return Device Position: 0 (1) 31 > 31 Disabled Set Delay for ARD (Automayic Return Device) mode: 0 (10) 2550 s Lobby Park Option: 0 Disabled 1 Enabled Select CTL or PKS switch: 0 CTL switch is connected 1 PKS switch is connected Parking Service Position: 0 (1) 31 > 31 Disabled Parking Shutoff Type: 0 ETO 1 NAO 2 ETO with door open after shutdown Parking Shutoff Time: 0 (1) 255 s PKS default door: 0 Both doors will open at PKS-P 1 Only front door opens 2 Only rear door opens Enable Separate Hall Buttons: 0 Normal HB-operation 1 Rear HB as Separate Riser Time until DCP-mode (delayed car protection): 25 (1) 255 s CTL default door (car to any landing): 0 Both doors will open at CTL-P 1 Only front door opens 2 Only rear door opens

Symbol
CPR-T

Purpose and Range

ARD-P

255

ARD-T

L-PARK

CTL/PKS

PKS-P

255

PKS-TY

PKS-T

PKS-DO

EN-SHB

10

DCP-T

50

11

CTL-DO

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 6 / 25 : 27-Jun-1995

OCSS (continued):
No.
12

Version: GAA 30082 BAC Purpose and Range


CTL (Car To Any Landing) position: 0 (1) 31 > 31 Disabled ANS (anti nuisance service): 0 Disabled >0 Number of calls to trigger ANS ATT (Attendant Service) type: 0 Start with DCB or RDCB 1 Start with ATTU or ATTD 2 NAO (USA) Independent Service: 0 Start on CCB 1 Start on DCB 2 Start on ISD/ISU 3 NAO (USA) Select Car To Landing Type: 0 ETO 1 NAO Speech Mode: 0 Floor message on CC only 1 Floor message also on HC Door Reopen Count: 0 No limit 1 (1) 255 Number of allowed door reopenings Disable CCs behind moving car: 0 CCs behind allowed 1 CCs behind not allowed Disable DOB button: 0 DOB/RDOB always enabled 1 DOB disabled if door closed 2 RDOB disabled if door closed 3 Both disabled if door closed

Symbol
CTL-P

Default
255

13

ANS

14

ATT

15

ISC

16

CTL-TY

17

SPEECH

18

DOC

19

DS-CCB

20

DS-DOB

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 7 / 25 : 27-Jun-1995

Group:
No.
0

Version: GAA 30082 BAC Default


1 Car identifier in group: 1 (1) 3 Number of cars in group: 1 (1) 3 Cars parking in Lobby: 1 (1) 3 MIT (Moderate incomming traffic) Startdelay: 0 (1) 255 s MIT Time-Out: 0 (1) 255 s MIT Variable Interval Dispatch: 0 (1) 255 s Dual Up Peak Border Position: 0 (1) 31 > 31 Disabled Dual Up Peak Group: 0 Car belongs to subgroup 1 1 Car belongs to subgroup 2 MOT (Moderate Outgoing traffic) Time-Out: 0 (1) 255 s Enable Up Call Bypass: 0 Disabled 1 Enabled Transfer Floor Position: 0 (1) 31 > 31 Disabled Park Clock Position 1: 0 (1) 31 > 31 Disabled Park Clock Position 2: 0 (1) 31 > 31 Disabled

Symbol
GRP-NO

Purpose and Range

GROUP

CNL

MIT-ST

MIT-T

MIT-VD

DUPK-P

255

DUPK-G

MOT-T

EN-UCB

10

TFS-P

255

11

PARK-1

255

12

PARK-2

255

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 8 / 25 : 27-Jun-1995

Group (continued):
No.
13

Version: GAA 30082 BAC Purpose and Range


Park Clock Position 3: 0 (1) 31 > 31 Disabled Park Clock Position 4: 0 (1) 31 > 31 Disabled Park Clock Position 5: 0 (1) 31 > 31 Disabled Park Clock Position 6: 0 (1) 31 > 31 Disabled Park Clock Position 7: 0 (1) 31 > 31 Disabled Park Clock Position 8: 0 (1) 31 > 31 Disabled Enable separate basement zone: 0 No free car parks in basement zone 1 A free car parks in basement zone

Symbol
PARK-3

Default
255

14

PARK-4

255

15

PARK-5

255

16

PARK-6

255

17

PARK-7

255

18

PARK-8

255

19

EN-ZBS

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 9 / 25 : 27-Jun-1995

Drive:
No.
0

Version: GAA 30082 BAC Default


1 Drive Type: 0 1-SP 1 2-SP, G-L 2 G-S/D 3 G-L with SL 4 G-L with SL 5 2-SP, G-L 6 G-S/D 7 SPEC60 8 G-D NAO 9 G-D NAO 10 MOT-VLV 11 SOL-VLV 12 MOT-VLV 13 SOL-VLV 14 LSVF 15 LSVF 16 LSVF-W 17 LSVF-W

Symbol
DRIVE

Purpose and Range

XADO XADO XADO ADO ADO ADO XADO ADO ADO ADO XADO XADO ADO XADO ADO XADO

C-TYPE

Controller Type: 0 MCS 310 1 MCS 310 CA, HY 2 MCS 120, MCS 220 3 MCS 220 M 1A Time: 0 (0.1) 25.5 s 2A Time: 0 (0.1) 25.5 s DDP Time (fast run): 0 (1) 45 s 3P Time (slow run): 0 (1) 45 s Speed (fast run mode): 25 40 63 100 160 175 250 cm/s

(Europa 2000) (Cargo 2000) (OTIS 2000) (OTIS 2000)

1AT

2AT

DDP

32

3P

32

SPEED

100

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 10 / 25 : 27-Jun-1995

Drive (continued):
No.
7

Version: GAA 30082 BAC Purpose and Range


Enable Motor Protection Device: 0 Disabled 1 Enabled Motor Protection Device Time: 0 (1) 254 s 255 wait forever Hydro Drive Type for Hydro: 0 Star - Delta 1 Soft 2 Direct Set Star/Soft Time for Hydro: 0 (0.1) 25.5 s Set Star/Delta gap / add. Soft Time (L+UX) for Hydro: 0.06 (0.004) 0.2 s Set delay between UX and UXT for Hydro: (contract option) 0 (0.1) 1 s Enable PLS1 (Oil-Max-Pressure Limit Switch) for Hydro: 0 Disabled 1 Enabled Enable OTS (Oil-Over Temperature Switch) for Hydro: 0 Disabled 1 Enabled Select ACD (Anti Creeping Device) or UXT output for Hydro: 0 ACD and UXT disabled 1 ACD enabled 2 UXT enabled (contract option) Set Power Off delay for LSVF-W 0, 255 Disabled 1 (1) 254 s Set Power On delay for LSVF-W 8 (1) 20 s

Symbol
EN-MPD

Default
0

MPD-T

10

HY-TYP

10

L-T

10

11

UX-D

20

12

UXT-D

13

EN-PLS

14

EN-OTS

15

ACD/UXT

16

P-OFF-D

17

P-ON-D

10

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 11 / 25 : 27-Jun-1995

Drive (continued):
No.
18

Version: GAA 30082 BAC Purpose and Range


Enable 3-Phase Detection (J-Relay) 0 Disabled 1 Enabled Number of periods necessary to detect a fault 0 (1) 4 Enable Brake Current Detection: 0 Disabled 1 Enabled Delay of BCD (after lifted brake) 0 (0.1) 10 s Max. fault time of BCD 0 (0.1) 10 s Delay of BCD (after fallen brake) 0 (0.1) 10 s

Symbol
EN-J

Default
1

19

J-T

20

EN-BCD

21

BON-D

10

22

BFLT-T

15

23

BOFF-D

15

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 12 / 25 : 27-Jun-1995

Doors:
No.
0

Version: GAA 30082 BAC Default


2

Symbol
DOOR

Purpose and Range


Type of Doors: 0 FLH 1 9550T & ACG 2 9550T & TLD / DO_2000 3 OVL / MRDS 4 OVL & ACG 5 DO_2000 6 MCG 7 Kiekert / MLI & ACG 8 Kiekert / MLI & TLD/CLD Type of Rear Doors: 0 FLH 1 9550T & ACG 2 9550T & TLD / DO_2000 3 OVL / MRDS 4 OVL & ACG 5 DO_2000 6 MCG 7 Kiekert / MLI & ACG 8 Kiekert / MLI & TLD/CLD Enable DDO (double door operation): 0 Disabled 1 Enabled Mixed Dooroperators: 0 Same operators front/rear 1 Different operators front/rear Type of Door Bypass circuit: 0 DBP operated (4-relay) 1 LVC operated (3-relay) select separate CM relay output (MCS220M) 0 (one door) CMR at RDC-output (P6:10) 1 (two doors) CMR at RSL (IO no. 785) NOTE: only applicable for FLH, MCG, ACG Limited Door Reversal: 0 Full DOB, full EDP, full LRD 1 Full DOB, limited EDP, full LRD Enable PMO (door time monitoring): 0 Disabled 1 Enabled

(DC-relay)

(DO-relay)

REAR

(DC-relay)

(DO-relay)

EN-DDO

MIXDOR

DBP-TY

SEL-CMR

LDR

EN-PMO

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 13 / 25 : 27-Jun-1995

Doors (continued):
No.
8

Version: GAA 30082 BAC Purpose and Range


Enable NDG (nudging): 0 Disabled 1 Enabled Nudging Time: 0 (1) 255 s Enable Cancel Doortime with CCB: 0 Disabled 1 Enabled Debouncing Time of Door Contact DW: 0 (0.1) 25.5 s Open Door Bell Timer: 0 (0.1) 25.5 s Min Doortime Car: 0 (0.1) 25.5 s Max Doortime Car: 0 (0.1) 25.5 s Min Doortime Hall: 0 (0.1) 25.5 s Max Doortime Hall: 0 (0.1) 25.5 s Door reverse time: 0 (0.004) 1 s Rear door reverse time: 0 (0.004) 1 s Door Close Protection Time: 10 (1) 255 s Door Open Protection Time: 10 (1) 255 s Lobby Door Time: 0 (0.1) 25.5 s Cafeteria Door Time: 0 (0.1) 25.5 s

Symbol
EN-NDG

Default
0

NDG-T

20

10

EN-CK

11

DW-DLY

10

12

DO-BEL

13

MIN-C

20

14

MAX-C

40

15

MIN-H

40

16

MAX-H

60

17

DOR-T

18

RDOR-T

19

DTC-T

20

20

DTO-T

20

21

LOB-NT

40

22

CFT-NT

40

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 14 / 25 : 27-Jun-1995

Doors (continued):
No.
23

Version: GAA 30082 BAC Purpose and Range


Special DOB Door Time: 0 (0.1) 25.5 s DHB Doortime: 0 (1) 255 s Wild Car Door Time: 0 (0.1) 25.5 s Shabat Door Time: 0 (0.1) 25.5 s Shabat Lobby Door Time: 0 (0.1) 25.5 s MPD/Hydro Door Open Time: 0 (1) 255 s DXT Time (extended door time): 0 (0.1) 25.5 s

Symbol
SPB-NT

Default
0

24

DHB-T

120

25

WCO-T

26

SHO-T

27

SHO-LT

28

DAR-T

60

29

DXT-T

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 15 / 25 : 27-Jun-1995

Position Reference
No.
0

Version: GAA 30082 BAC Purpose and Range


Leveling Mode: 0 DZ-STP 1 LV-STP stop with DZ: use DZ-DLY (in 4 ms units) stop with LVU/LVD: for CA-MOD=0 (RLEV-2): set LV-U-D, LV-D-D = 0 for CA-MOD=1 (RLEV-3): use LVU-5D, LVD-5D (in 4 ms units) stop with DZ, 1LV/2LV: use LV-U-D, LV-D-D (in 4 ms units) stop with IPU, IPD: (for 1-Speed Drive) use IPU-D, IPD-D (unit depends on T-BASE) stop with UIS, DIS: (for Hydraulic Drive) use LV-U-D for DIS (in 4 ms units) use LV-D-D for UIS (in 4 ms units)

Symbol
LV-MOD

Default
2

2 3

DZ-STP IP-STP

UIS/DIS

Note: auto-stop for - Gamma S/D, Spec_60 and Dynalift on RUN signal (110V input) - LSVF-W on RN (coded inputs) 1 DZ-TYP 0 DZ coding: 0 DZ = 1LV 1 DZ = 1LV and 2LV 2 POSY operation (if neither RLV nor ADO) to stop: DZ = 1LV and 2LV after stop: DZ = 1LV or 2LV Delay for DZ: 0 (0.004) 1 s

DZ-DLY

(LV-MOD = 0)

LV-U-D

12

Delay for DZ, 1LV/2LV (in up direction): 0 (0.004) 1 s (LV-MOD = 1, 2, 4) Delay for DZ, 1LV/2LV (in down direction): 0 (0.004) 1 s (LV-MOD = 1, 2, 4) Timebase for IPU-D, IPD-D, 1LS-D and 2LS-D: 0 0.1 s 1 0.004 s Delay for IPU: 0 (0.1) 25.5 s 0 (0.004) 1 s Delay for IPD: 0 (0.1) 25.5 s 0 (0.004) 1 s

LV-D-D

12

T-BASE

IPU-D

(T-BASE=0) (T-BASE=1)

IPD-D

(T-BASE=0) (T-BASE=1)

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 16 / 25 : 27-Jun-1995

Position Reference (continued):


No.
8

Version: GAA 30082 BAC Purpose and Range

Symbol
1LS-D

Default
0 Delay for 1LS: 0 (0.1) 25.5 s 0 (0.004) 1 s Delay for 2LS: 0 (0.1) 25.5 s 0 (0.004) 1 s Enable RLV operation: 0 Disabled 1 Enabled RLV - Type: 0 RLV 1 DRLV Limit of RLV steps: 0 (1) 255

(T-BASE=0) (T-BASE=1)

2LS-D

(T-BASE=0) (T-BASE=1)

10

EN-RLV

11

RLV-TY

Relevelling Delayed Relevelling (using DIS1)

12

RL-CNT

13

RL-DIS

255

Set RLV time up (DIS lost): 0 (0.1) 25.5 s Set RLV time down (UIS lost): 0 (0.1) 25.5 s 0 (0.004) 1 s (hydraulic drive) Set RLV delay up: 0 (0.004) 1 s Set RLV delay down: 0 (0.004) 1 s

14

RL-UIS

255

15

RL-U-D

16

RL-D-D

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 17 / 25 : 27-Jun-1995

Cargo:
No.
0

Version: GAA 30082 BAC Default


0

Symbol
CA-MOD

Purpose and Range


CARGO mode: 0 RLEV/RLEV-2 1 RLEV-3 2 Class-C2 Delay for LV stop (UP 0.5 load): 0 (0.004) 1 s Delay for LV stop (DOWN 0.5 load): 0 (0.004) 1 s Class C2: time-out for Bolts In: 0 (0.004) 1 s Class C2: time-out for Bolts Out: 0 (0.004) 1 s Class C2: time-out for Move Up: 0 (0.004) 1 s Class C2: time-out for Move Down: 0 (0.004) 1 s Class C2: time-out for PLS4: 0 (0.004) 1 s

(not authorized yet)

LVU-5D

LVD-5D

BI-T

BO-T

MVU-T

MVD-T

PLS4-T

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 18 / 25 : 27-Jun-1995

Emergency:
No.
0

Version: GAA 30082 BAC Default


0

Symbol
ES-TYP

Purpose and Range


Define ES-Type: 0 ESS connected 1 ESB connected (closed door will remain closed) 2 ESB connected (closed door will open) 3 ES-input disabled (for LCB_II version GCA 21240 D2 / D3) EFO (emergency fireman operation) position: 0 (1) 31 > 31 Disabled EFO with doors closed: 0 Disabled 1 (1) 255 s DC time EFO default door: 0 Both doors will open at EFO position 1 Only front door opens 2 Only rear door opens EFO override option: 0 No override possible 1 XEFO input overrides EFO after arrival at return landing 2 After EFS no EFO is permitted if EFO or AEFO are still active 3 Functions 1 + 2 together Enable nudging speed for EFO 0 Door closes with full speed 1 Door closes with nudging speed

R)
1 EFO-P 255

EFO-DC

EFO-DO

EFO-OP

EFONDG

ASL-P

255

ASL (alternate service landing) position: 0 (1) 31 > 31 Disabled Type of EFS (Emergency Fireman Service) (if EFK (ASL) connected): 0 EFO 1 EFS 1 (Aut.) 2 EFS 2 (Man.) 3 ANSI (USA) 4 British Standard 5 Swiss Standard 6 Australia 7 New Zealand 8 EFS 2 (Man. with ESK)

EFS-TY

R)

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 19 / 25 : 27-Jun-1995

Emergency (continued):
No.
8

Version: GAA 30082 BAC Purpose and Range


EFS default door: 0 Both doors will open position 1 Only front door opens 2 Only rear door opens EFS return time (time EFK must be low to force car back to EFO landing if EFK is switched on again while in EFS): 0-39 Function disabled 40-255 Time (in 100 ms units) EFK must be low Enable E2P-backup of EFO/EFS: 0 Disable backup 1 Enable backup Hardware position reference: 0 Disabled 1 One contact per floor 2 Binary coded contacts 3 Signal at every odd floor EPO (emergency power operation) Position: 0 (1) 31 EPO A/C (position) EPO E (hydro: bottom) = 32 EPO B/D (next floor) EPO F (hydro: next floor down)w >32 Disabled EPO with doors closed: 0 Disabled 1 (1) 255 s EPO default door: 0 Both doors will open at EPO position 1 Only front door opens 2 Only rear door opens EPO priority if EFO/EFS: 0 No prio for EPO 1 EPO has priority Earthquake Operation Type: 0 California 1 New Zealand

Symbol
EFS-DO

Default
0

EFS-RT

10

EN-BAK

11

HDWPOS

12

EPO-P

255

13

EPO-DC

14

EPO-DO

15

EPO-PR

16

EQO

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 20 / 25 : 27-Jun-1995

Emergency (continued):
No.
17

Version: GAA 30082 BAC Purpose and Range


Express Priority Service: x0 automatic ISC x1 return to normal x2 automatic CHCS 0x immediate return 1x stop at next commitable 2x serve car calls en route EHS time-out: 0 Disabled 1 (1) 255 s

Symbol
EPS-TYP

Default
0

18

EHS-T

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 21 / 25 : 27-Jun-1995

Security:
No.
0

Version: GAA 30082 BAC Default


0

Symbol
EN-FPD

Purpose and Range


Enable FPD (fireproof doors): 0 Disabled 1 Enabled Enable IST (intermittent stop): 0 Disabled 1 In up direction only 2 In down direction only 3 In both directions 5 In up direction only, if ISTS active 6 In down direction only, if ISTS active 7 In both directions, if ISTS active Intermittent Stop Position: 0 (1) 31 >31 Disabled Enable CRO (card reader operation): 0 Disabled 1 Single contact reader 2 Australian Card Key sec type 2 3 Australian Card Key sec type 1 4 Multi contact reader General Control of Buttons type: 0 disabled 1 GCB_1 2 GCB_2 RIOT Operation Position: 0 (1) 31 >31 Disabled

EN-IST

IST-P

255

EN-CRO

GCBTYP

RIOT-P

255

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 22 / 25 : 27-Jun-1995

Security (continued):
No.
6

Version: GAA 30082 BAC Purpose and Range


Secure Access Type: 1 SAC enabled, without ISC override 3 SAC enabled, with ISC override 5 SAC enabled, without ISC override, clear only if sec. enabled 7 SAC enabled, with ISC override, clear only if security enabled else SAC disabled

Symbol
SACTYP

Default
0

SAC-D1

255

Secure Access digit 1: 0 (1) 6 >6 Disabled Secure Access digit 2: 0 (1) 6 >6 Disabled Secure Access digit 3: 0 (1) 6 >6 Disabled

SAC-D2

255

SAC-D3

255

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 23 / 25 : 27-Jun-1995

Test:
No.
0

Version: GAA 30082 BAC Symbol


TPOS 1

Default
255

Purpose and Range


Test position 1 (automatic test run): 0 (1) 31 > 31 Disabled Test position 2 (automatic test run): 0 (1) 31 > 31 Disabled Test Delay for automatic test run: 0 (1) 255 s Disable safety check: address of TCI, 1LS and 2LS regarding to Std-IO-List 0 RSL safety check enabled 1 RSL safety check disabled Disable DW-check during NOR: 0 DW is checked when door open 1 No DW-check during NOR Debug Parameter: 0 (1) 255 s Debug Parameter 1: 0 (1) 255 s Enable Init_1CL: default position (Mot_VLV.): 0 Disabled 1 Enabled Enable storage of 10 events into E2PROM: 0 Disabled 1 Enabled Enable contract handling: Operate up to 32 openings: 0 Disabled 1 Enabled

TPOS 2

255

TDELAY

255

NoAdrChk

NoDW_Chk

DEBUG

DEBUG1

EN-1CL

EN-EVT

EN-CRT

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 24 / 25 : 27-Jun-1995

Index
A

ACD/UXT, 10 ANS, 6 ARD-P, 5 ARD-T, 5 ASL-P, 18 ATT, 6 B BFLT-T, 11 BI-T, 17 BOFF-D, 11 BON-D, 11 BOTTOM, 2 BO-T, 17 C CA-MOD, 17 CFT-NT, 13 CFT-P, 2 CNL, 7 CONFIG, 2 CPC-TYP, 4 CPR-T, 5 CR-DIR, 4 CTL-DO, 5 CTL-P, 6 CTL-TY, 6 CTL/PKS, 5 C-CHK, 4 C-TYPE, 9 D DAR-T, 14 DBP-TY, 12 DCP-T, 5 DDP, 9 DEBUG, 23 DEBUG1, 23 DHB-T, 14

DOC, 6 DOOR, 12 DOR-T, 13 DO-BEL, 13 DRIVE, 9 DS-CCB, 6 DS-DOB, 6 DTC-T, 13 DTO-T, 13 DUPK-G, 7 DUPK-P, 7 DW-DLY, 13 DXT-T, 14 DZCNT, 4 DZ-DLY, 15 DZ-TYP, 15 E EFONDG, 18 EFO-DC, 18 EFO-DO, 18 EFO-OP, 18 EFO-P, 18 EFS-DO, 19 EFS-RT, 19 EFS-TY, 18 EHS-T, 20 ELD-DOOR, 3 ELD-fCLG, 2 ELD-fOPG, 2 ELD-LNG, 3 ELD-MSG, 3 ELD-rCLG, 3 ELD-rOPG, 2 ELD-Sym1, 3 EN-BAK, 19 EN-BCD, 11 EN-BSM, 2 EN-CK, 13 EN-CRO, 21 EN-CRT, 23 EN-DDO, 12 EN-DZI, 4 EN-EVT, 23

EN-FPD, 21 EN-HLC, 3 EN-IST, 21 EN-J, 11 EN-MPD, 10 EN-NDG, 13 EN-OTS, 10 EN-PLS, 10 EN-PMO, 12 EN-RLV, 16 EN-RR, 4 EN-SFR, 3 EN-SHB, 5 EN-UCB, 7 EN-ZBS, 8 EN-1CL, 23 EPO-DC, 19 EPO-DO, 19 EPO-P, 19 EPO-PR, 19 EPS-TYP, 20 EQO, 19 ERO-TYP, 4 ES-TYP, 18 G GCBTYP, 21 GROUP, 7 GRP-NO, 7 H HDL-TY, 3 HDWPOS, 19 HL-SET, 3 HY-TYP, 10 I IPD-D, 15 IPU-D, 15 ISC, 6 IST-P, 21

Part

OTIS
European and Transcontinental Operations

: 4 - AA 3 :
GCA 21240 D VIIIa

FIELD COMPONENT MANUAL


Software Data

No.

Vintage : 01 / 8

PRODUCT ADMINISTRATION

MCS - LCB_II
List of Installation Parameters

Page Date

: 25 / 25 : 27-Jun-1995

J J-T, 11 L LDR, 12 LOBBY, 2 LOB-NT, 13 LR-T, 3 LVD-5D, 17 LVU-5D, 17 LV-D-D, 15 LV-MOD, 15 LV-U-D, 15 L-PARK, 5 L-T, 10 R M MAX-C, 13 MAX-H, 13 MD/AES, 4 MIN-C, 13 MIN-H, 13 MIT-ST, 7 MIT-T, 7 MIT-VD, 7 MIXDOR, 12 MOT-T, 7 MPD-T, 10 MVD-T, 17 MVU-T, 17 N NDG-T, 13 NoAdrChk, 23 NoDW_Chk, 23 O OPERAT, 2 T P PARK-1, 7

PARK-2, 7 PARK-3, 8 PARK-4, 8 PARK-5, 8 PARK-6, 8 PARK-7, 8 PARK-8, 8 PI, 2 PKS-DO, 5 PKS-P, 5 PKS-T, 5 PKS-TY, 5 PLS4-T, 17 P-OFF-D, 10 P-ON-D, 10

TPOS1, 23 TPOS2, 23 T-BASE, 15 U UXT-D, 10 UX-D, 10 W WCO-T, 14 1 1AT, 9 1LS-D, 16 2 2AT, 9 2LS-D, 16 3 3P, 9

RDOR-T, 13 REAR, 12 RIOT-P, 21 RLV-TY, 16 RL-CNT, 16 RL-DIS, 16 RL-D-D, 16 RL-UIS, 16 RL-U-D, 16 S SACTYP, 22 SAC-D1, 22 SAC-D2, 22 SAC-D3, 22 SEL-CMR, 12 SHO-LT, 14 SHO-T, 14 SPB-NT, 14 SPEECH, 6 SPEED, 9

TDELAY, 23 TFS-P, 7 TOP, 2